<< E-Mon Additional Metering Components,
Software & Accessories
E-Mon D-Mon Run-Time Sensor
|
|
The E-Mon D-Mon run-time sensor is designed to provide "run-time"
information through the Class
3000 meter or IDR
when used with E-Mon EnergyTM
software. The split-core current transformer (CT) allows the
unit to be installed without need of a contact or switch on the
monitored equipment. When the CT is clamped around the conductor
being monitored it senses the current flowing through the conductor.
The contact is wired to the external input terminal of the meter or
IDR. A current flow of 2 to 50 amps causes the run-time sensor to
close its normally open internal contact (form A). When the contact
closes, it can be set up to register in the meter or IDR as a
software-created count of 300 pulses per minute. This is used to
account for the run-time of the equipment (as a percentage) in 5 or
15 minute intervals. |
|

|
| |
The E-Mon D-Mon run-time sensor operates without the
need of a power supply or a voltage input. The unit can be mounted
up to 500 feet away from the meter or IDR. The contact is rated at
120 VAC/DC max with a current handling maximum of 100 milliamps (0.1
amps).
| Specifications |
| Maximum Switch Voltage |
120 VAC/DC |
| Maximum Switch Amps |
0.1 (100 mA) |
| CT Operating Range |
2 to 50 amps |
| CT Short-Term Rating |
200 amps |
| CT Inside Dimensions |
0.875 x 1.375 (inches) |
| Switch Enclosure Dimensions |
3.8 x 2.4 x 1 (inches) |
| CT Secondary Wire Rating |
600 VAC |
|
| |
|
|
E-Mon Catalog |
E-Mon Pricelist

$25.00 Minimum on Total Order
____________________________________________________________
99 Washington Street, Melrose, MA 02176
781.665.1400 | 800.517.8431 | Fax: 781.665.0780 | Email:
Copyright © Fotronic Corporation
All Rights Reserved